GD2G Ex-proof Infrared Gas Detectors

Flammable Gas Detecting Solutions

ATEX and IECEx Certified

Durable

Reliable Measurement

GD2G Series

Ex-proof Infrared Gas Detectors

For precise detection of combustible gases and carbon dioxide gas. Easily integrated into your security system with relay outputs and 4-20mA analog output.

Quick Specs

GD2G Infrared Fixed Gas Detectors detect flammable-explosive gases with high sensitivity. It does not require frequent calibration and has a long lifetime. Infrared sensor technology does not measure based on a chemical reaction like catalytic or electrochemical sensors. They work on the principle of measuring the absorption amount of infrared rays in different gases. They are not affected by temperature, pressure and other gases which are harmful effects in the environment. In this way, it provides high performance and does not require continuous calibration, does not require maintenance and provides a longer-lasting solution.

GD2G Infrared Fixed Gas Detectors have an advanced micro-controller chip in the smart circuit board. Its embedded software algorithm guarantees perfect detection under all conditions. It also enables software optimizations according to the needs of your facility.

GD2G Infrared Fixed Gas Detectors can be used as an independent device with digital relay outputs (NOC), and can be easily integrated into your control and automation system thanks to its industrial standard 4-20mA analog outputs. It reacts immediately if target gas is detected at the lower and upper alarm limits you have specified. Dangerous conditions for the safety of your staff and facility are avoided before they grow.

Power

24 VDC ± 25%

Detection Range *

0 - 100% LEL

Resolution **

1% LEL

Response Time ***

< 30s

Sensor Type

Infrared

Analog Output

4~20 mA

Digital Output

3 Relays (NO or NC)

Environmental Conditions

Temperature: -20/+60°C

Pressure: 86-106 kPa

Humidity: 95% RH

Weight

1kg

Material

Aluminum

Sensor Capsule

Stainless Steel

ATEX Marking

II 2G Ex d IIC Gb T6

IECEX Marking

Ex db IIC T6 Gb

IP Protection Level

IP65

Warranty

2 Years

* For carbon dioxide 0 – 5000 ppm, 0 – 1% volume, 0 – 2% volume, 0 – 5% volume
** For carbon dioxide 1% of detection range
*** For carbon dioxide T(50) < 20s; T(90) < 60s

Order Code

Gas Name

Formula

Range

GD2GI01V0100

Methane

CH4

0-100 %vol

GD2GI02V0100

Propane

C3H8

0-100 %vol

GD2GI01L0100

Methane

CH4

0-100 %LEL

GD2GI02L0100

Propane

C3H8

0-100 %LEL

GD2GI08P5000

Carbondioxide

CO2

0-5000 ppm

GD2GI08V0001

Carbondioxide

CO2

0-1 %vol

GD2GI08V0005

Carbondioxide

CO2

0-5 %vol

GD2GI30L0100

Acetone*

C3H6O

0-100 %LEL

GD2GI39L0100

Benzene*

C6H6

0-100 %LEL

GD2GI31L0100

Cyclohexane*

C6H12

0-100 %LEL

GD2GI32L0100

Cyclopentane

C5H10

0-100 %LEL

GD2GI40L0100

Difluoroethane (R152a)

C2H4F2

0-100 %LEL

GD2GI41L0100

Dimethyl Ether

C2H6O

0-100 %LEL

GD2GI42L0100

Ethane

C2H6

0-100 %LEL

GD2GI33L0100

Ethanol*

C2H6O

0-100 %LEL

GD2GI22L0100

Isobutane*

C4H10

0-100 %LEL

GD2GI46L0100

Isobuthylen

C4H8

0-100 %LEL

GD2GI43L0100

Methyl-Ethyl-Ketone

C4H8O

0-100 %LEL

GD2GI36L0100

Methanol*

CH4O

0-100 %LEL

GD2GI17L0100

n-Butane

C4H10

0-100 %LEL

GD2GI16L0100

Pentane

C5H12

0-100 %LEL

GD2GI38L0100

Propylene

C3H6

0-100 %LEL

GD2GI04L0100

Toluene*

C7H8

0-100 %LEL

GD2GI27V0002

Etylene

C2H4

0-2.3 %vol